Standard remote controls Electrical Actuator BIFFI
Network Type
Comments
Analog Module
Analog Position Transmission Module (APTM)
This card features a 4 to 20 mA galvanically-insulated module for position or torque re-transmission. The said card is easily plugged into the base card without the need for dedicated tools. The module can be configured to the output torque in place of the actuator position.
Position Servo Amplifier Module (PSM
Module necessary for actuators in modulating and inching duty. It drives the motor through pulses at constant frequency and duration proportional to the position error, following an externally-set analogical point signal. The basic features are:
Input: 4 to 20 mA or 0 to 20 mA with galvanic insulation.
Output: 4 to 20 mA with galvanic insulation for position or torque re-transmission.
HART 7
Electrical interface: 4 to 20 mA analog loop, 2-wire communication
Data rate: Request/response mode - 2/3 updates per second Optional burst mode - 3/4 updates per second
Bus type: HART® protocol 7.9
Device number:
Point-to-point architecture: 1 field device Split ranging: normally 2 field devices Multidrop: 16 field devices
Bus length:
Maximum twisted pair length - 3,048 m / 10,000 ft Maximum multiple twisted pair length - 1,524 m / 5,000 ft
Electrical power:
Actuator powered Maximum voltage 36 V Minimum voltage 0 V
Profibus
Electrical interface: 2-wire RS-485
Data rate: 9.6 19.2 45.45 93.75 187.5 500 1,500 Kbit/s
Network topology: Line (bus) structure. With repeaters tree structures can also be realized
Device number: 32 devices per segment without repeater (maximum 126 with repeaters)
Transmission technology : Profibus DP
Bus length
Dependent on bus speed selected
Bus speed
9.6
19.2
45.45
93.75
187.5
500
1,500
kbit/s
Length:
1200
200
200
200
m
Electrical power: Actuator-powered (optional auxiliary external voltage supply)
Station type: DPV1 and DPV2 (redundancy) slave
Foundation Fieldbus
Electrical interface: IEC 61158-2, 2-wire communication
Data rate: 31.25 kbit/s
Bus type: H1 communication bus, Voltage Mode signaling
Device number: 32 devices per segment - Maximum 16 devices (best practice) even less in case of many Function Blocks assigned to the microcycle
Bus length: 1900 m per segment
Electrical power: Bus-powered - Maximum voltage 32 V - Minimum voltage 9 V - Rated current In = 19 mA - Fault current Imax = 24 mA
LonWorks
Electrical interface: 2-wire twisted pair
Data rate: 78 Kbps
Network topology: Multi-drop line or loop
Device number: 60 devices per segment using specific 16 AWG cable. More segments with repeaters
Transmission technology: LonWorks® FT-10
Bus length: 800 m per segment using specific 16 AWG cable. More segments with repeaters
Electrical power: Actuator-powered